EX ZS 80 AL-3D
ATEX emergency pull-wire switches- Ex zone 22
- Metal enclosure
- 2 contacts
- Position indicator and integrated emergency-stop push button
- Wire length up to 100 m
- Spring force variant: 100 N
- Lever for release and position indication
- Watertight collar
- Wire pull and breakage detection
Features
Technical Data
| Applied standards | EN IEC 60079-0, EN 60079-31, EN 60947-5-1, EN 60947-5-5, EN ISO 13849-1, EN ISO 13850 |
| Enclosure | aluminium die-cast, powder-coated, RAL 1003 |
| Cover | aluminium die-cast, powder-coated, RAL 9005 |
| Degree of protection | IP65 (EN IEC 60079-0 + IEC/EN 60529), IP67 (IEC/EN 60529) |
| B10d (10 % load) | 200 000 |
| TM | max. 20 years |
| Contact material | silver |
| Switching system | slow action, positive break NC contacts A |
| Switching elements | 1 NC/1 NO contact or 2 NC contacts, type Zb |
| Connection | cable H05VV-F |
| Cable cross-section | 4 x 0.75 mm² (incl. conductor ferrules) |
| Cable length | 3 m |
| Rated impulse withstand voltage Uimp | 4 kV |
| Rated insulation voltage Ui | 250 V |
| Conventional thermal current Ithe | 6 A |
| Utilisation category | AC-15 |
| Rated operating current/voltage Ie/Ue | 6 A/250 VAC; 0.25 A/230 VDC |
| Short-circuit protection | 6 A gG/gN fuse |
| Ambient temperature | –20 °C … +65 °C |
| Mechanical life | > 100 000 operations |
| Max. wire length | 100 m |
| Note | At 5 m distance intermediate wire supports are required. One wire thimble is provided. |
| Impact energy | max. 7 J |
| Ex marking | L II 3D Ex tc IIIC T80°C Dc |
Variants
| Name | Article No.: |
|---|---|
| Ex ZS 80 1Ö/1S WVD AL-3D 3m | 1270746 |
| Ex ZS 80 2Ö WVD AL-3D 3m | 1344150 |


















